EWYQ016CAWP |
EWYQ021CAWP |
EWYQ025CAWP |
EWYQ032CAWP |
EWYQ040CAWP |
EWYQ050CAWP |
EWYQ064CAWP |
Cooling capacity
|
Nom.
|
kW
|
17.0 (1)
|
21.2 (1)
|
25.5 (1)
|
31.8 (1)
|
42.3 (1)
|
50.7 (1)
|
63.3 (1)
|
Capacity control
|
Method
|
|
Inverter controlled
|
Inverter controlled
|
Inverter controlled
|
Inverter controlled
|
Inverter controlled
|
Inverter controlled
|
Inverter controlled
|
|
Minimum capacity
|
%
|
25
|
25
|
25
|
25
|
25
|
25
|
25
|
Power input
|
Cooling
|
Nom.
|
kW
|
5.81 (1)
|
7.47 (1)
|
9.45 (1)
|
12.7 (1)
|
15.1 (1)
|
19.0 (1)
|
25.5 (1)
|
EER
|
2.93
|
2.84
|
2.70
|
2.50
|
2.80
|
2.67
|
2.48
|
Dimensions
|
Unit
|
Depth
|
mm
|
774
|
774
|
774
|
774
|
780
|
780
|
780
|
|
|
Height
|
mm
|
1,684
|
1,684
|
1,684
|
1,684
|
1,684
|
1,684
|
1,684
|
|
|
Width
|
mm
|
1,370
|
1,370
|
1,370
|
1,680
|
2,360
|
2,360
|
2,980
|
Weight
|
Unit
|
kg
|
280
|
332
|
332
|
414
|
604
|
604
|
765
|
Casing
|
Colour
|
|
Daikin White
|
Daikin White
|
Daikin White
|
Daikin White
|
Daikin White
|
Daikin White
|
Daikin White
|
|
Material
|
|
Polyester coated galvanised steel plate
|
Polyester coated galvanised steel plate
|
Polyester coated galvanised steel plate
|
Polyester coated galvanised steel plate
|
Polyester coated galvanised steel plate
|
Polyester coated galvanised steel plate
|
Polyester coated galvanised steel plate
|
Air heat exchanger
|
Type
|
|
Air cooled coil
|
Air cooled coil
|
Air cooled coil
|
Air cooled coil
|
Air cooled coil
|
Air cooled coil
|
Air cooled coil
|
Fan
|
Quantity
|
|
1
|
1
|
1
|
2
|
2
|
2
|
4
|
|
Type
|
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Fan motor
|
Drive
|
|
Direct drive
|
Direct drive
|
Direct drive
|
Direct drive
|
Direct drive
|
Direct drive
|
Direct drive
|
Compressor
|
Quantity
|
|
1
|
2
|
2
|
3
|
4
|
4
|
6
|
|
Type
|
|
Hermetically sealed scroll compressor
|
Hermetically sealed scroll compressor
|
Hermetically sealed scroll compressor
|
Hermetically sealed scroll compressor
|
Hermetically sealed scroll compressor
|
Hermetically sealed scroll compressor
|
Hermetically sealed scroll compressor
|
Operation range
|
Air side
|
Cooling
|
Min.
|
°CDB
|
-5
|
-5
|
-5
|
-5
|
-5
|
-5
|
-5
|
|
|
|
Max.
|
°CDB
|
43
|
43
|
43
|
43
|
43
|
43
|
43
|
|
Water side
|
Evaporator
|
Min.
|
°CDB
|
-10 (4)
|
-10 (4)
|
-10 (4)
|
-10 (4)
|
-10 (4)
|
-10 (4)
|
-10 (4)
|
|
|
|
Max.
|
°CDB
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
Sound power level
|
Cooling
|
Nom.
|
dBA
|
78
|
78
|
78
|
80
|
81
|
81
|
83
|
Refrigerant
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
|
GWP
|
|
2,087.5
|
2,087.5
|
2,087.5
|
2,087.5
|
2,087.5
|
2,087.5
|
2,087.5
|
|
Circuits
|
Quantity
|
|
1
|
1
|
1
|
1
|
2
|
2
|
2
|
Power supply
|
Phase
|
|
3N~
|
3N~
|
3N~
|
3N~
|
3N~
|
3N~
|
3N~
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
|
Voltage
|
V
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
|
Voltage range
|
Min.
|
%
|
-10
|
-10
|
-10
|
-10
|
-10
|
-10
|
-10
|
|
|
Max.
|
%
|
10
|
10
|
10
|
10
|
10
|
10
|
10
|
Unit
|
Starting current
|
Max
|
A
|
0.0 (9)
|
77.7
|
78.7
|
88.7
|
99.8
|
101.9
|
120.7
|
|
Running current
|
Max
|
A
|
22.2
|
25.3
|
26.4
|
35.2
|
47.4
|
49.6
|
67.2
|
Notes
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
(1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C
|
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
|
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
(3) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
|
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
(4) - Water can be used above 5°C. Between 0°C and 5°C a 30% glycol solution (propylene or ethylene) has to be used. Between 0°C and -10°C a 40% glycol solution (propylene or ethylene) has to be used (see installation manual and information related to OPZL opti
|
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
(5) - Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
|
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
(6) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
|
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
(7) - This is PD between inlet & outlet connections of unit. It includes the water side heat exchanger pressure drop.
|
|
(8) - Including piping + PHE; excluding expansion vessel
|
(8) - Including piping + PHE; excluding expansion vessel
|
(8) - Including piping + PHE; excluding expansion vessel
|
(8) - Including piping + PHE; excluding expansion vessel
|
(8) - Including piping + PHE; excluding expansion vessel
|
(8) - Including piping + PHE; excluding expansion vessel
|
(8) - Including piping + PHE; excluding expansion vessel
|
|
(9) - No peak current because of inverter compressor
|
(9) - No peak current because of inverter compressor
|
(9) - No peak current because of inverter compressor
|
(9) - No peak current because of inverter compressor
|
(9) - No peak current because of inverter compressor
|
(9) - No peak current because of inverter compressor
|
(9) - No peak current because of inverter compressor
|